How does a BMS control lighting, and when is DALI worth it?
Paweł Skowron, lead automation engineer, IQ-BuildingUpdated:
Not every lighting circuit needs the BMS: where motion sensors do the job, integration is often unnecessary. Other circuits are worth controlling from one place, by schedules and astronomical time. DALI pays off where zones, scenes and dimming are needed, above all in large halls: switching off or dimming a zone during breaks and between shifts adds up to hundreds of kilowatt-hours a day.
Which circuits to integrate
- Green wall lighting simulates daylight and runs during the day.
- External lighting, such as terraces, follows astronomical time and runs only at night, with an optional offset from sunrise and sunset.
- Other circuits follow ordinary schedules or manual control.
A common alternative is a stand-alone astronomical time switch on each circuit. These are not cheap, at PLN 1,000 or more each, and they are awkward to live with: each one controls only its own circuit, so every change means walking round the building from board to board. In the BMS all circuits are set from one screen.
Critical circuits
Some circuits cost money the moment they fail, for example illuminated signs. We fit pulse-output energy meters on them, which are simple and cheap to install. The BMS compares energy draw with the expected value, so even a partial failure triggers a notification.
What DALI adds
On request we deliver lighting in DALI. Every luminaire has its own address, which allows zones to be regrouped without rewiring, scenes and smooth dimming, wall panel control and a separate schedule for each zone.
Production hall: dimming during breaks
In one large production plant we addressed more than 1,500 DALI luminaires across several halls. Lighting there follows detailed zone schedules: it is switched off or dimmed between shifts and during 15–30 minute breaks.
A worked example to show the scale. Assumptions: 1,500 luminaires at an assumed 150 W each (225 kW), three shifts, one 30-minute break per shift dimmed to 20%.
| Quantity | Value |
|---|---|
| Lighting load | 1,500 × 150 W = 225 kW |
| Power saved while dimmed to 20% | 225 kW × 0.8 = 180 kW |
| Dimmed time per day | 3 × 0.5 h = 1.5 h |
| Saving per day | 180 kW × 1.5 h = 270 kWh |
Time between shifts and zones left unused on a given day come on top of that.
Questions and answers
Do motion-sensor circuits need the BMS?
Usually not. Motion sensors already limit lighting hours well.
How does the BMS detect a failed sign?
By a drop in energy draw measured by the pulse-output meter on that circuit.