How does a BMS control car park ventilation, and how much energy can it save?

Paweł Skowron, lead automation engineer, IQ-BuildingUpdated:

A BMS runs car park ventilation when it is needed – at peak traffic times or in a selected mode – rather than around the clock, ideally guided by air quality sensors instead of a fixed timetable. Safety systems, meaning gas detection and the fire system, always take priority: the BMS neither replaces nor competes with them, it complements them. In a car park with several dozen fans, the gap between continuous running and a schedule can exceed one megawatt-hour a day.

Who decides when the fans run?

An underground car park has a fire system, gas detection (carbon monoxide, LPG) and everyday ventilation. The first two are safety systems. They have overriding priority and work independently of the BMS.

The BMS does not replace safety systems. If gas is detected or the fire system operates, ventilation runs as safety requires, whatever schedule is set in the BMS.

What the BMS adds

  • Zone-by-zone ventilation control with ECO and COMFORT modes and schedules.
  • The status of every zone and fan on one screen.
  • A history of gas sensor readings for each zone.

That history reveals recurring events, such as LPG being detected in the same zone again and again, so the maintenance team can look for the cause.

A worked example

One building running our system has 75 jet fans of about 1 kW each, roughly 75 kW in total. The figures below show the scale; they are a calculation, not a measurement.

ScenarioHours per dayEnergy per day
All fans around the clock24 h75 kW × 24 h = 1,800 kWh
Ventilation at the morning and afternoon peaks2 × 2 h = 4 h75 kW × 4 h = 300 kWh
Difference1,500 kWh per day

The real result depends on the number and rating of the fans, the zoning and how often gas detection starts the ventilation. Exhaust fumes peak when cars arrive and leave, so the schedule should follow those hours and drop to a minimum at night and at weekends.

Air quality sensors instead of a fixed timetable

The best basis is multi-gas air quality sensors that continuously measure carbon monoxide, nitrogen dioxide (mainly from diesel engines), particulates and, where needed, LPG. They work differently from the CO/LPG detectors of the safety system, which raise an alarm only once a threshold is crossed. An air quality sensor shows concentrations starting to rise, which in practice shows when people arrive and leave.

From this data the BMS works out how the car park is used and sets the ventilation schedule itself. The schedule then adjusts automatically as habits change, for example when people leave earlier on Fridays. Gas detection stays in charge of safety throughout; air quality sensors do not replace it.

Questions and answers

Can the BMS switch ventilation off while gas is detected?

No. Gas detection and the fire system have priority over scheduled ventilation.

Why record gas sensor readings?

To spot recurring problems, such as regular LPG detections in one zone, and remove the cause.