How can a BMS cut chiller energy use?

Paweł Święch, founder and technical leader, IQ-BuildingUpdated:

A chiller looks after its own internal control, including master–slave sequencing. The BMS adds three things: a chilled water temperature that follows outdoor temperature (a setpoint curve), operating modes and schedules matched to how the building is used, and continuous monitoring of compressors and pumps. The chiller then never produces colder water than is needed, and does not run for an empty building. The BMS can also act ahead of time, for example pre-cooling the building at night before a hot day, and vary the speed of the circulation pumps.

Chiller controls versus the BMS

Chillers have manufacturer controls that protect the compressors and share load between units, for example in a master–slave arrangement. The BMS does not interfere with that. It covers what the chiller controls do not: the weather forecast, the energy tariff, whether the building is occupied and what water temperature the systems really need. In one building running our system, the chillers have a combined electrical rating of more than 1 MW.

A setpoint curve instead of one fixed temperature

The colder the water, the more energy the chiller uses. A fixed low setpoint all season means paying for a margin that is needed only on the hottest days. In our interface the chilled water setpoint follows a curve based on outdoor temperature, with separate curves for ECO and COMFORT modes. The curve is edited on the chiller screen.

Modes, schedules and monitoring

  • COMFORT mode when the building is in use; ECO mode outside working hours.
  • Switching by schedule or manually.
  • For each chiller: which unit is master and which is slave, plus start counts and run hours for every compressor and pump.
  • Chilled water flow and return temperatures on the same screen.

Start counts matter: a compressor that cycles too often wears faster. On a trend this is visible straight away.

Pre-cooling and variable-speed pumps

The BMS can control cooling ahead of demand. If a very hot day is forecast and the building’s tariff allows it, the system pre-cools the building overnight. The chillers then run on cheaper electricity and at a lower outdoor temperature, which means a better COP, and less cooling is needed during the day.

Chilled water or glycol circulation pumps often run at constant flow all the time and are only switched on and off; we know this from one of the buildings we work with. Where the pumps have variable-speed drives, the BMS can match their output to cooling demand. The saving on the pumps alone can be large, because pump power falls roughly with the cube of speed: at 80% speed it is about half.

What else is possible?

  • Locking chillers out below a set outdoor temperature.
  • Metering chiller electricity and comparing it with weather and occupancy.
  • Chiller alarms shown in the BMS with the rest of the building, not only on the unit on the roof.

Questions and answers

Does the BMS control master–slave sequencing?

Usually not. The chiller controls do that. The BMS shows the status and sends parameters such as the water temperature setpoint.

Can every chiller be integrated?

It depends on the manufacturer. Sometimes a communication module is enough; sometimes integration is not available.