How much do electric air curtains cost to run, and how can they be kept under control?

Maciek Dembski, technical manager, IQ-BuildingUpdated:

Far more than the purchase price suggests. In one building, two electric air curtains in the reception, rated at 10 kW each, use PLN 8,000–10,000 of electricity in a frosty month. Where curtains are already electric, they should be integrated with the BMS: controlled by temperature and schedule, with supply air temperature, power draw and fan operation monitored.

Cheap to buy, expensive to run

Air curtains are like steam humidifiers: the electric version is cheaper to buy and easier to fit, so it wins at construction stage. Over the life of the building it is not the optimal choice. A 10 kW curtain running continuously uses 240 kWh a day, more than 7,000 kWh a month.

A fault nobody noticed for a month

In one building, before BMS integration, a curtain fan failed. The curtain was controlled by a local controller, so the heater kept heating for a month with no airflow. Nobody noticed: the curtain hung high in an open atrium and the heat rose. The result was several thousand PLN of wasted electricity and a heater running without cooling, which is a fire risk.

What BMS integration adds

  • Control: fan speed and heating output matched to outdoor and entrance-zone temperature.
  • Schedule: different operation on working days, at night and at weekends.
  • Power measurement: current draw in kilowatts for each curtain.
  • Supply air temperature and fan run confirmation: a heater working without airflow raises an alarm straight away.

Flexible control

An integrated curtain does not have to run one way all season. At night, with the doors closed, it is switched off completely. On a frosty day it runs gently at low speed and boosts the airflow for a moment when the doors open. Where the door controls allow it, the BMS receives a signal that someone is approaching from outside and starts the curtain before the doors open, so even less cold air gets in. Above a set outdoor temperature the heater is locked out. Before the building opens, the curtains and entrance heating start ahead of time. After the heater switches off, the fan runs on briefly to cool it. And when the building approaches its contracted capacity, the BMS can briefly limit the heating output.

Questions and answers

What should the BMS monitor in an electric air curtain?

Supply air temperature, power draw and confirmation that the fan is running.