Knowledge base

How does a BMS detect flooding before water reaches the switchroom?

Paweł Święch, founder and technical leader, IQ-BuildingUpdated:

With three independent levels. The first watches the power supply to the drainage pumps, the second the water level in the sumps, and the third the floor of rooms that must be protected, such as main switchrooms. Each level catches what the previous one missed, and the alarm comes before water gets to where it does damage.

LevelWhat is monitoredWhat it tells you
1Power supply to drainage pumpsThe pump will not run
2Water level in sumpsThe pump is not running or cannot keep up
3Leak sensors in roomsWater has reached a protected area

Level 1. Drainage pumps remove rainwater from collecting sumps. They also work in lift pits, often the lowest point of a building, where the same monitoring makes sense. If their supply fails, the BMS raises an alarm and the pump icon turns red. No water has arrived yet, but nothing will pump it out.

Level 2. Level sensors in the sumps signal a failed pump or one that cannot keep up, for example in a downpour. The supply can be fine while the pump still is not working.

Level 3. Leak sensors are placed in key locations, above all main switchrooms. Any one of them triggers a common alarm.

The same supervision helps with separators. A separator is usually a tank with a pump, and they do sometimes overflow, which is a very smelly problem. The BMS trends when the separator pumps ran, shows the float switches and raises an alarm when the level is exceeded.

Questions and answers

Why is a floor sensor alone not enough?

Because it reports only when water is already in the room. Monitoring the pumps and sump levels gives time to react earlier.

All articles