How do you know trace heating is actually working?

Maciek Dembski, technical manager, IQ-BuildingUpdated:

Not from the breaker status. An auxiliary contact only tells you the protective device has not tripped, while the cable can be damaged and cold with the circuit switched on. Only a measurement gives certainty: an energy meter on the heating circuit shows whether the cable draws power and whether that power is within set limits.

Why trace heating is critical

Trace heating protects pipework and roof drainage from freezing. If it fails in a frost, the result is a burst pipe and a flood, and usually nobody knows about the failure until then.

LevelWhat the BMS showsWhat it misses
Auxiliary contacts on protective devicesWhether a device has trippedWhether the cable is heating
Energy meter on the circuitWhether the circuit draws power, and how much—

How we do it

  • We fit pulse-output energy meters on heating circuits. They are simple and cheap to install.
  • The BMS checks that an energised circuit really draws energy and that the draw is within limits.
  • Too little means a damaged cable or an open circuit; too much is also a reason to investigate.
  • Cables switch on by outdoor temperature, with a threshold set in the interface.

Electric heaters

Buildings also have electric heaters, for example in plant rooms. In one building six groups totalling 20 kW could use up to 1 MWh if left on over a weekend. The heaters do have their own thermostats, but a thermostat only caps the temperature: a heater set to a high, comfortable temperature keeps holding it when nobody needs the heat. Whether heating is needed at all is decided by the BMS, which assigns each group to one of three schedules, as with small extract fans.

Questions and answers

Is a breaker signal enough to monitor trace heating?

No. It only shows whether the device has tripped. A cable can be cold with the breaker closed.