How can office air conditioning be controlled so that empty rooms are not heated or cooled?
Paweł Skowron, lead automation engineer, IQ-BuildingUpdated:
Integrate the room controllers with the BMS. People still set the temperature they like, while the system handles the rest: outside working hours it switches fan coil units off or lowers their settings, limits the temperature range, stops two units in one room from heating and cooling at the same time, and shuts air conditioning down when a window is open. Working hours are about 23% of the month; the other 77% is time when the system can do less.
What the BMS shows
A floor plan with every controller and its status; for each one the current temperature, valve positions and warnings; a zone overview with its schedule; and a temperature trend per controller. Setpoint, fan speed and mode can also be changed from the BMS.
Four mechanisms that cut waste
- Zone schedule. Outside working hours all fan coil units in the zone are off or at minimum settings, and resume shortly before people arrive.
- Limited range. Users adjust the setpoint within set limits, for example 20–24°C, so extremes such as 16 or 26°C are not available.
- No fighting. Two controllers in one open-plan office, one cooling and one heating: the temperature stays the same and energy is used twice. The system prevents this.
- Window contacts. Opening a window switches off the fan coil units in that room.
What it delivers
Five working days of eight hours are about 23% of the month. For the remaining 77% air conditioning can be off or run at reduced settings. Diagnostics improve too: the maintenance team sees a faulty zone or controller in the system instead of learning about it from a tenant.
A side note on fan power. The fan in a fan coil unit draws little, from a few dozen to just over a hundred watts. For one office area with 69 units we calculated an average fan load of about 7 kW. Running all year round, that is about PLN 55,000 of electricity; on a schedule of 10 hours on working days and 2 hours on other days, about PLN 17,000. The figures assume PLN 0.89 per kWh and cover the fans only, not heating or cooling. On a whole office floor of about 5,000 m² gross with around a hundred such units, continuous running comes to about PLN 80,000 a year and the same schedule to about PLN 25,000.
Every setpoint change is recorded. The data shows which zones people keep adjusting, and in which direction, which is the basis for correcting schedules or base setpoints for good. Our IQ Assistant app helps spot these patterns; the maintenance team decides what to change.
The system can be fitted in new fit-outs and in occupied space. In occupied space we work mainly at weekends, with prefabricated components, so tenants are not disturbed.
Questions and answers
Do users lose control of the temperature?
No. They can still change the setpoint on their controller, within the agreed range.
Where does 23% come from?
Five days of eight hours are 40 of the 168 hours in a week, just under 24%.