Is it worth connecting small extract fans to the BMS?
Maciek Dembski, technical manager, IQ-BuildingUpdated:
Yes. A single small extract fan typically draws 30–100 W, but a building has several dozen of them and, left alone, they run around the clock, including nights and weekends. Most do not need to. Connecting them to the BMS and running them on schedules cuts operating hours by roughly two thirds.
A worked example
Besides air handling units and car park ventilation, a building has many small extract fans in toilets, utility rooms and plant rooms. For a building with 40 fans averaging 60 W:
| Scenario | Hours per year | Energy per year |
|---|---|---|
| Running around the clock | 8,760 h | 2.4 kW × 8,760 h ≈ 21,000 kWh |
| Schedule: working days, 12 h a day | approx. 3,000 h | 2.4 kW × 3,000 h ≈ 7,200 kWh |
| Difference | approx. 13,800 kWh per year |
There is also a cost the fan meter does not show: every extract fan removes air that the building has already paid to heat or cool.
How the BMS controls them
- On/off fans follow schedules. Our interface offers three schedules, and each fan is assigned to one of them.
- Every fan can also be switched to manual control.
- Variable-speed fans are controlled by an analogue signal or a frequency inverter.
- One click takes you from the fan list to the floor plan showing where the fan is.
Some rooms need constant ventilation, so not every fan is scheduled the same way.
Questions and answers
How much power does a small extract fan use?
Usually 30–100 W. The cost comes from the number of fans and their running hours, not from the rating of one unit.