How should a VAV ventilation system be controlled to avoid wasting energy?

Paweł Skowron, lead automation engineer, IQ-BuildingUpdated:

A VAV system uses the least energy when the duct static pressure setpoint is continuously adjusted to the damper positions of the VAV boxes – a strategy called static pressure reset. The fan then runs only as hard as needed to keep the worst-placed box almost fully open. Constant fan speed and a fixed pressure setpoint both work, but most of the time they spend energy on throttling.

Why balancing with manual dampers is not enough

An air handling unit pushes air into a duct network, and the fan creates the static pressure that drives it. With no dampers at all, air takes the easiest path: short branches near the unit get too much, distant ones too little.

Manual dampers fix this at commissioning, but only for one pressure. Say the system was balanced at 300 Pa. After 4 pm half the occupants leave and you halve the pressure to 150 Pa: flow in the near branches drops a little, while the far branches get almost nothing. The balance no longer holds.

The incentive to slow the fan is large, because fan power falls with the cube of speed: half the speed needs one eighth of the power.

What a VAV box does

A VAV (variable air volume) box sits in the duct and combines a damper, an actuator and an airflow sensor. The BMS sends a setpoint, for example 200 m³/h, and the box positions its damper until that flow is measured. Each zone gets its own airflow whatever the others are doing, and a loss of flow raises an alarm straight away.

Three ways to control the fan

StrategyWhat drives the fanDrawback
Constant speedNothing – fixed speed sized for the worst caseConstant throttling, noise, highest energy use
Constant static pressurePressure sensor in the main ductPressure is higher than needed most of the time
Static pressure resetDamper positions of the VAV boxesBoxes must report damper position

Constant speed. The fan speed is fixed for the worst case, with every zone open. That rarely happens, so the boxes throttle the excess. It is hardly used today.

Constant static pressure. The fan speed follows a fixed pressure setpoint in the main duct. When a zone opens, pressure drops and the fan speeds up. This is much better, but the setpoint is chosen for near-maximum load.

Static pressure reset. The controller reads the damper positions and keeps adjusting the pressure setpoint. If most dampers are nearly closed, there is too much pressure, so the fan slows down instead of the dampers throttling. The target state: the worst-placed box is almost fully open.

What did the study find?

Static pressure reset is one of three strategies in ASHRAE Guideline 36, alongside supply air temperature reset and zone airflow control. A simulation study by Kun Zhang et al. (“Estimating ASHRAE Guideline 36 energy savings for multi-zone variable air volume systems using Spawn of EnergyPlus”, Journal of Building Performance Simulation, 2022) compared Guideline 36 sequences with typical control across 243 scenarios for a medium-sized office.

  • Average HVAC energy savings: 31% – for all three Guideline 36 strategies applied together, not for static pressure reset alone.
  • Highest result: 76%, in the San Francisco climate with low internal loads and long operating hours, comparing the most basic control with the best – a simulation maximum, not a figure to expect everywhere.
  • Static pressure reset was the most effective single strategy in every climate studied.

What we see on site confirms that static pressure reset gives the most of the three. We use these algorithms wherever the system allows it.

Example: process ventilation in a laboratory

In one of our projects the extract system serves process machines, fume cupboards and chemical storage cabinets. The cabinets are ventilated around the clock at a constant flow. Workstations have a push-button: the operator switches extraction on, the VAV box receives a new setpoint and a lamp lights when the flow is reached.

The VAV boxes there could not report damper position, so we used a constant pressure setpoint. Replacing them would have been costly because they would have to be explosion-proof units, about five times the price of standard ones.

Questions and answers

Can static pressure reset be added to an existing system?

Yes, provided the VAV boxes report damper position to the controller. Otherwise the options are constant static pressure or new boxes.

Is it enough to slow the fan down after hours?

Not with manual dampers. At lower pressure the air follows branch resistance and distant zones are left almost unventilated.

This article is based on an episode from the IQ-Building YouTube channel (in Polish): Jak sterować VAV? Strategie regulacji przepływu w HVAC