Why are steam humidifiers so expensive to run in office buildings, and how can the cost be cut?

Maciek Dembski, technical manager, IQ-BuildingUpdated:

A steam humidifier is cheap to buy and easy to fit, but every kilogram of steam takes about 0.75 kWh of electricity, and in hard water the cylinders scale up and need regular replacement. Three things cut the cost: moisture recovery in the air handling unit, integrating the humidifier with the BMS so that it runs only when needed, and water treatment suited to the humidifier type.

Why are steam humidifiers so common?

Electric steam humidifiers are increasingly fitted in office buildings because they are relatively cheap to buy, simple to install and compact. The bill arrives later, in operation.

Where the cost comes from

Electricity. A steam humidifier boils water with electricity. Heating and evaporating one kilogram of water takes about 0.75 kWh. A single humidifier serving an office air handling unit is rated at tens of kilowatts, sometimes as much as 100 kW.

Cylinders. Limescale builds up in the cylinder until it has to be replaced. With hard water and no water treatment system this can happen after about two months of operation, sometimes after just one. We know an office complex where the cylinders alone cost about PLN 80,000 a year: there are more than a dozen humidifiers, some with four cylinders each, and they are replaced several times a year. That figure does not include the time of the in-house technicians who do the work.

No water treatment. Many buildings have no water treatment for humidifiers. Treatment does not reduce energy use, but it extends cylinder life.

How it often ends

The humidifiers often stay switched off because they cost too much to run. They are turned on only when a tenant measures humidity and reports that the air is out of specification. The building owns expensive equipment it does not use, and tenants get dry air.

What cuts the cost?

Moisture recovery. An enthalpy heat exchanger transfers part of the water vapour from extract air to supply air, along with heat. The more moisture is recovered, the less the humidifier has to add. This can cut humidification costs considerably, but it needs a suitable heat exchanger in the air handling unit.

BMS integration. Where steam humidifiers already exist, integration is the key. The humidifier should run only when needed, not boil water continuously. The BMS:

  • controls it against measured humidity and a setpoint,
  • enables it only when the air handling unit is running and there is airflow,
  • switches it off outside occupied hours,
  • shows its status and alarms, including cylinder exhaustion,
  • trends humidity, so a faulty sensor becomes visible.

Water treatment. Well-chosen water treatment slows scaling. It has to match the humidifier type: electrode humidifiers need water within a certain conductivity range, so follow the manufacturer's requirements.

What happens without integration?

We know of a case where the duct humidity measurement was wrong and the humidifier was not properly integrated with the BMS. It never received a signal to stop and kept boiling water until the ventilation duct was flooded. Proper integration gives the humidifier a stop signal and the maintenance team an alarm.

Questions and answers

How much energy does a steam humidifier use?

About 0.75 kWh per kilogram of steam, so a unit producing 100 kg of steam per hour draws roughly 75 kW.

Can humidification be made cheaper without replacing the humidifiers?

Yes. BMS control based on actual humidity and schedules helps, as does water treatment chosen to the humidifier manufacturer's requirements. Moisture recovery needs a suitable heat exchanger in the air handling unit.